● Channel: 12 channel DC circuits:
● Rated Voltage: DC -48V
● 12 Channels Hall Current Sensor:Hall sensor secondary side DC 5V access
● RS485(MODBUS-RTU)
● Din Rail
Model |
Basic Function |
AMC200L-12DE |
It can be connected to 12 single-phase DC circuits at the same time, can directly measure parameters such as voltage, |
Technical Parameter |
Technical Indicator |
|
Input |
DC Voltage |
One channel:DC -48V |
|
DC Current |
12 Channels Hall Current Sensor:Hall sensor secondary side DC 5V access |
|
State Grid Monitoring |
One channel:DC 0-5V |
|
Overload |
Voltage: 1.2 times for 1 second, 2 times for 1 second; Current: 1.2 times for 1 second, 10 times for 1 second |
Frequency |
||
Resolution |
The voltage output accuracy is 0.01V, the current output accuracy is 0.01A, |
|
Function |
Basic Function |
Monitoring equipment system time, total voltage, total output current, total power, total electrical energy, |
|
Alarm Function |
DC voltage output too low alarm, DC voltage output too high alarm, one-time power-off alarm, |
|
Timing function |
Support broadcast timing, remote timing |
|
Communication |
|
|
Hall power supply |
A set of ±12V power output |
|
Humidity And Temperature |
4 Channels NTC Temperature Monitoring:Temperature:-20-100℃(Accuracy±2℃) Humidity:20-90%RH(Accuracy ±5%RH) |
Auxiliary power |
Voltage Range |
DC -40V~-60V |
|
Power consumption |
The whole device≤2W (without Hall power supply output) |
Storage |
It has the storage function of historical energy data and historical alarm information |